| Membrane cleaning and fouling control in a pilot plant of ultrafiltration for drinking water treatment |
| Authors: ZHU Dan1, GU Ping1, WANG Haiyan1, HE Fenghua2, HAN Tao2 |
| Units: School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China;2Tianjin TEDA Waterworks Company, Tianjin 300457, China |
| KeyWords: drinking water;membrane fouling;backwashing;chemical enhanced backwash (CEB); chemical cleaning;pre-chlorination |
| ClassificationCode:TU 991.2 |
| year,volume(issue):pagination: 2012, 32(4):81-86 |
|
Abstract: |
|
A pilot-scale low pressure ultrafiltration membrane system was used to treat the finished water from a sedimention tank in the waterworks, and membrane fouling control was investigated. Physical backwashing, chemical enhanced backwash (CEB), chemical cleaning and pre-chlorination were studied for membrane fouling control. Results showed that physical backwashing have a little effect on fouling control, however, CEB, an online cleaning mode could have a great effect on fouling control, and the average recovery rate of specific flux was 85%. The effect of chemical cleaning with oxalic acid was better, after cleaning, the average SF value was increased to 265 L/(h•m2•bar). Pre-chlorination could slow down the fouling rate. In addition, the composition of the eluent was analysed. The results revealed that iron and dissolved organic matter were the major factors for fouling. |
|
Funds: |
|
AuthorIntro: |
| 朱丹(1987-),女,陕西宝鸡,硕士研究生,从事饮用水膜法处理研究。 *通讯联系人,022-27405059, |
|
Reference: |
|
[1] 刑卫红, 童金忠, 王焕章, 等. 微滤和超滤过程中浓差极化和膜污染控制方法研究[J]. 化工进展, 2000(1): 44-48.
|
|
Service: |
| 【Download】【Collect】 |
《膜科学与技术》编辑部 Address: Bluestar building, 19 east beisanhuan road, chaoyang district, Beijing; 100029 Postal code; Telephone:010-80492417/010-80485372; Fax:010-80485372 ; Email:mkxyjs@163.com